Design MPC Controller for Plant with Delays

This example shows how to design an MPC controller for a plant with delays using MPC Designer.

Plant Model

An example of a plant with delays is the distillation column model:

[y1y2]=[12.8es16.7s+118.9e3s21.0s+13.8e8.1s14.9s+16.6e7s10.9s+119.4e3s14.4s+14.9e3.4s13.2s+1] [u1u2u3]

Outputs y1 and y2 represent measured product purities. The model consists of six transfer functions, one for each input/output pair. Each transfer function is a first-order system with a delay. The longest delay in the model is 8.1 minutes.

Specify the individual transfer functions for each input/output pair. For example, g12 is the transfer function from input u2 to output y1.

g11 = tf(12.8,[16.7 1],'IOdelay',1.0,'TimeUnit','minutes');
g12 = tf(-18.9,[21.0 1],'IOdelay',3.0,'TimeUnit','minutes');
g13 = tf(3.8,[14.9 1],'IOdelay',8.1,'TimeUnit','minutes');
g21 = tf(6.6,[10.9 1],'IOdelay',7.0,'TimeUnit','minutes');
g22 = tf(-19.4,[14.4 1],'IOdelay',3.0,'TimeUnit','minutes');
g23 = tf(4.9,[13.2 1],'IOdelay',3.4,'TimeUnit','minutes');
DC = [g11 g12 g13;
      g21 g22 g23];

Configure Input and Output Signals

Define the input and output signal names.

DC.InputName = {'Reflux Rate','Steam Rate','Feed Rate'};
DC.OutputName = {'Distillate Purity','Bottoms Purity'};

Alternatively, you can specify the signal names in MPC Designer, on the MPC Designer tab, by clicking I/O Attributes.

Specify the third input, the feed rate, as a measured disturbance (MD).

DC = setmpcsignals(DC,'MD',3);

Since they are not explicitly specified in setmpcsignals, all other input signals are configured as manipulated variables (MV), and all output signals are configured as measured outputs (MO) by default.

Open MPC Designer

Open MPC Designer importing the plant model.

mpcDesigner(DC)

MPC Designer window, showing the closed loop step response. The plant inputs are on the left hand side, and the plant outputs are on the right hand side.

Since DC is a stable, continuous-time LTI plant, MPC Designer sets the controller sample time to 0.1 Tr, where Tr is the average rise time of the plant. Since DC has a Tr of is around 33 minutes, MPC Designer sets a sample time of 3 minutes.

MPC Designer imports the specified plant to the Data Browser. The following objects are also created and added to the Data Browser:

  • mpc1 — Default MPC controller created using DC as its internal model.

  • scenario1 — Default simulation scenario.

The app runs the simulation scenario and generates input and output response plots.

Specify Prediction and Control Horizons

For a plant with delays, it is good practice to specify the prediction and control horizons such that

pm+max(Td)Ts

where,

  • p is the prediction horizon.

  • m is the control horizon.

  • max(Td) is the maximum delay, which is 8.1 minutes for the DC model.

  • Δt is the controller Sample time, which is 3 minutes for the DC model.

On the Tuning tab, in the Horizon section, specify a Sample time of 1, a Prediction horizon of 30, and a Control horizon of 5.

MPC Designer window top left section, showing the horizon section of the tuning tab, with Sample time, Prediction, and Control horizon settings.

After you change the horizons, the Input Response and Output Response plots for the default simulation scenario are automatically updated.

Simulate Controller Step Responses

On the MPC Designer tab, in the Scenario section, click Edit Scenario > scenario1. Alternatively, in the Data Browser, right-click scenario1 and select Edit.

In the Simulation Scenario dialog box, specify a Simulation duration of 50 minutes.

In the Reference Signals table, in the Signal drop-down list, select Step for both outputs to simulate step changes in their setpoints.

Specify a step Time of 0 for reference r(1), the distillate purity, and a step time of 25 for r(2), the bottoms purity.

Upper section of the Simulation Scenario dialog box.

Click OK.

The app runs the simulation with the new scenario settings and updates the input and output response plots.

MPC Designer window, showing the updated closed loop step responses.

The Input Response plots show the optimal control moves generated by the controller. The controller reacts immediately in response to the setpoint changes, changing both manipulated variables. However, due to the plant delays, the effects of these changes are not immediately reflected in the Output Response plots. The Distillate Purity output responds after 1 minute, which corresponds to the minimum delay from g11 and g12. Similarly, the Bottoms Purity output responds 3 minutes after the step change, which corresponds to the minimum delay from g21 and g22. After the initial delays, both signals reach their setpoints and settle quickly. Changing either output setpoint disturbs the response of the other output. However, the magnitudes of these interactions are less than 10% of the step size.

Additionally, there are periodic pulses in the manipulated variable control actions as the controller attempts to counteract the delayed effects of each input on the two outputs.

Improve Performance Using Manipulated Variable Blocking

Use manipulated variable blocking to divide the prediction horizon into blocks, during which manipulated variable moves are constant. This technique produces smoother manipulated variable adjustments with less oscillation and smaller move sizes.

To use manipulated variable blocking, on the Tuning tab, specify the Control horizon as a vector of block sizes, [5 5 5 5 10].

MPC Designer window, showing the closed loop step response with manipulated vatriable blocking.

The initial manipulated variable moves are much smaller and the moves are less oscillatory. The trade-off is a slower output response, with larger interactions between the outputs.

Improve Performance By Tuning Controller Weights

Alternatively, you can produce smooth manipulated variable moves by adjusting the tuning weights of the controller.

Set the Control horizon back to the previous value of 5.

In the Performance Tuning section, drag the Closed-Loop Performance slider to the left towards the Robust setting.

MPC Designer window, highlighting the Closed-Loop Performance slider being dragged to the left.

As you move the slider to the left, the manipulated variable moves become smoother and the output response becomes slower.

References

[1] Wood, R. K., and M. W. Berry, Chem. Eng. Sci., Vol. 28, pp. 1707, 1973.