Main Content

Model and Generate Code for Jump and Label Ladder Diagram Instructions

This example shows how to model a ladder diagram in Simulink® that uses the JMP and LBL instructions. Simulate the ladder diagram to verify its behavior and generate ladder diagram code from the model. The JMP and LBL instructions branch and loop the ladder diagram code.

Open the Model

The model consists of:

  • A PLC Controller Suite block namedSequentialMotorController that implements the JMP and LBL instructions and other logic to control motors

  • The blocks in the Human Machine Interface (HMI), which you can use to interact with the model

Open the model.

mdl = "LadderDiagramJmpAndLblModel";
open_system(mdl);

HMI Section

The HMI section contains blocks that you can use to interact with the model simulation. This image shows the components of the HMI section:

This HMI section contains:

  • Inputs: You can use the Sensor 2, Sensor 3, and Sensor 4 rocker switches to change the value of the respective inputs. When the rocker switch is in the On position, the value of the corresponding input is 1.

  • Graphs: The Dashboard Scope blocks display the status of Sensor2, Sensor3, Sensor4, Motor2, Motor3, and Motor4 signals, against time as the model simulation progresses.

PLC Controller Suite Block

The PLC Controller Suite block named SequentialMotorController block contains a Program block that houses the ladder logic. To view the ladder logic, open SequentialMotorController, Task block, and then the Program block. This image shows the ladder logic implementation that uses the JMP and LBL instructions for branching and looping.

The first rung contains the normally open (XIC) contact and a JMP block that jumps to the label Motor4 when Sensor4 is on. Rungs two and three turn on Motor2 and Motor3 based on the states of Sensor2 and Sensor3. Rung four contains the LBL instruction with the name Motor4.

Simulate and Validate the JMP and LBL Instructions

JMP and LBL instructions are elements in ladder diagrams that control branching and looping in the control logic. The JMP instruction enables conditional branching, which allows the control logic to choose between different paths. The LBL instruction enables looping, which allows the control logic to repeat a set of instructions until a certain condition is met. The JMP and LBL instructions should be used together and the LBL instruction should be the first instruction on a rung. To validate the ladder diagram model:

  • Ensure that rungs two and three execute normally when the JMP and LBL instructions are disabled.

  • The outputs on rungs two and three do not change state when the JMP and LBL instructions are enabled.

Before simulating and validating the mode, load the built-in data types, by using the plcloadtypes function.

plcloadtypes

To ensure that rungs two and three execute normally, turn on the Sensor2 and Sensor3 rocker switches in the top model and simulate the model. The Dashboard Scope blocks indicate that Motor2 and Motor3 turn on as soon as Sensor2 and Sensor3 turn on.

To ensure that rungs two and three do not execute when the JMP and LBL instructions are enabled, turn on Sensor4, turn off Sensor2 and Sensor3 and simulate the model. Motor4 turns on and Motor2 and Motor3 stay on. This image shows that after Sensor4 turn on and Sensor2 and Sensor3 turn off, Motor2 and Motor3 stay on.

Generate Code

After validating the operation of the JMP and LBL instructions, generate code for the PLC Controller Suite block. To generate ladder diagram code use the plcgeneratecode function:

generatedFiles = plcgeneratecode("LadderDiagramJmpAndLblModel/SequentialMotorController");

See Also

|

Related Topics