Flow Coefficient Parameterized Valve (TL)

Valve with flow area modeled in terms of its Cv or Kv flow coefficient

  • Flow Coefficient Parameterized Valve (TL) block

Libraries:
Simscape / Fluids / Thermal Liquid / Valves & Orifices

Description

The Flow Coefficient Parameterized Valve (TL) block models the flow characteristics of a valve using the flow coefficient as a means to relate the flow rate through the ports to the pressure drop across them. The flow coefficient parameterization suits those cases in which the internal geometry of a valve is known in poor detail or in which the flow coefficient is the preferred means of characterizing a valve. The valve model is sufficiently general in its assumptions that it can be applied to a variety of valves; no single valve type is assumed in this block.

Flow Coefficient Parameterization

The flow coefficient measures the ease with which a fluid driven by a pressure differential flows across a valve. It is an important parameter in the sizing of valves and a convenient way of characterizing one in a model. In this role it is especially useful, as it quantifies in a single number all of the losses incurred in the flow passages of the valve. The flow coefficient is typically measured by the valve manufacturer and reported in a data sheet provided for the valve.

Strictly speaking there are two flow coefficients in common use: Cv and Kv. These describe what is fundamentally the same quantity: the volumetric flow rate of water passing through a valve that has been opened to its maximum and set to some standard operating conditions. The flow coefficients differ only in the temperature and pressure drop established during the measurement (the operating conditions) and in the physical units used in its expression:

  • Cv is measured at a generally accepted temperature of 60 °F and pressure drop of 1 PSI; it is expressed in imperial units of US gpm. This is the flow coefficient used in the model when the Flow coefficient specification block parameter is set to Cv coefficient (USG/min) [1].

  • Kv is measured at a generally accepted temperature of 15 °C and pressure drop of 1 bar; it is expressed in metric units of m3/h. This is the flow coefficient used in the model when the Flow coefficient specification block parameter is set to Kv coefficient (m^3/h). [2].

Two values are required of the flow coefficient, a maximum and a minimum. The maximum corresponds to a valve open to full capacity; this is the value frequently reported in valve data sheets. The minimum corresponds to a valve closed tight, when only leakage flow remains, if any at all. This lower bound imposed on the flow coefficient serves primarily to ensure the numerical robustness of the model. Its exact value is less important than its being a (generally very small) number greater than zero.

Valve Opening Parameterization

The opening fraction of the valve (the ratio of the valve opening area to its maximum value) is determined during simulation from the input specified at port L. This input is the control signal and it is, in some valves, associated with stroke or lift percent. The control signal can range in value from 0 to 1. If a lesser or greater value is specified, it is adjusted to the nearest of the two limits. In other words, the signal is saturated at 0 and 1.

The conversion from control signal to opening fraction depends on the Valve opening characteristics parameterization selected in the block. The calculation result is the same for all parameterizations when the control signal is either 0 or 1: a value of 0 at port L always means a maximally (though not necessarily completely) closed valve; a value of 1 always means a maximally open valve. At intermediate values, the opening fractions differ:

  • Linear — The valve opening fraction (denoted f(L) in the figure) is equal to the control signal at port L. The two vary in tandem until the control signal either drops below zero (the valve is fully closed) or rises above its maximum value (the valve is fully open). The opening fraction ranges from 0 to 1 (a statement that does not apply to all valve opening parameterizations).

    f(L)=L.

  • Quick opening — The valve opening fraction, f(L), is a power function of the control signal at port L. The opening fraction rises quickly with the control signal at values near 0 and slowly at values near 1. The exponent (α) in the calculation determines how the opening rate changes with the control signal. The opening fraction ranges from 0 to 1.

    f(L)=L1α,α>1.

  • Equal percentage — The valve opening fraction is an exponential function of the control signal at port L. The opening fraction rises slowly with the control signal at values near 0 and quickly at values near 1. The base of the exponent (R, the rangeability of the valve, the ratio between the maximum and minimum flow rates through the ports) determines how the opening rate changes with the control signal. The opening fraction ranges from a small fraction (0.020.05 for typical rangeability values of 2050) to 1.

    f(L)=RL11R11R,R2050.

Mass Balance

The volume of fluid inside the valve, and therefore the mass of the same, is assumed to be very small and it is, for modeling purposes, ignored. As a result, no amount of fluid can accumulate there. By the principle of conservation of mass, the mass flow rate into the valve through one port must therefore equal that out of the valve through the other port:

m˙A+m˙B=0,

where m˙ is defined as the mass flow rate into the valve through the port indicated by the subscript (A or B).

Momentum Balance

The causes of those pressure losses incurred in the passages of the valve are ignored in the block. Whatever their natures—sudden area changes, flow passage contortions—only their cumulative effect is considered during simulation. It is this cumulative effect that the flow coefficient of the valve enables the block to capture in a model. This constant factors in the momentum balance of the valve indirectly, by way of the effective opening area (S) of the same:

pApB=m˙m˙2+m˙crρavgS2,

where:

  • p is the pressure at the port indicated by the subscript (A or B).

  • ρavg is the arithmetic mean of the fluid densities at the ports.

  • m˙ is the mass flow rate at a port.

  • m˙cr is the critical mass flow rate, that at which the flow is assumed to switch between laminar and turbulent regimes:

    m˙cr=Recrμavgπ4S,

    where Recr is the Reynolds number at the transition point and μavg is the average of the dynamic viscosities at the ports.

The effective opening area (S) is the product of scaling of the maximum opening area of the valve by the opening fraction (f(L)). The calculation imposes a lower bound on the opening area at which only leakage flow remains:

S(L)={Smaxf(L),if Smaxf(L)>SminSmin,else,

where the subscripts max and min refer to a valve in the fully opened and maximally closed positions; the function f(L) is the opening fraction calculated from the control signal specified at port L:

f(L)={L,Linear parameterizationL1/α,Quick opening parameterizationRL1,Equal percentages parameterization,

where α is obtained from the Exponent number block parameter and R from the Rangeability parameter. The maximum opening area is obtained by multiplying the (maximum) flow coefficient by an appropriate conversion factor:

SMax={λCCv,max,if Cv is usedλKKv,max,if Kv is used,

where:

  • λC is the conversion factor between the maximum flow coefficient in imperial units (Cv,max) and the maximum opening area: 2.4015e-5 m^2.

  • λK is the conversion factor between the maximum flow coefficient in SI units (Kv,max) and the maximum opening area: 2.7765e-5 m^2.

The minimum opening area in turn is obtained by multiplying the maximum opening area by the ratio between minimum and maximum flow coefficients:

SMin={Cv,minCv,maxSmax,if Cv is usedKv,minKv,maxSmax,if Kv is used.

Energy Balance

The valve is modeled as an adiabatic component. No heat exchange can occur between the fluid and the wall that surrounds it. No work is done on or by the fluid as it traverses from inlet to outlet. With these assumptions, energy can flow by advection only, through ports A and B. By the principle of conservation of energy, the sum of the port energy flows must then always equal zero:

ϕA+ϕB=0,

where ϕ is defined as the energy flow rate into the valve through one of the ports (A or B).

Ports

Input

expand all

Port through which to specify the signal that controls the opening of the valve (in certain valve types associated with stroke or lift percent). The valve is fully closed at a value of 0 and fully open at a value of 1.

Conserving

expand all

Opening through which the flow can enter or exit the flow resistance. Which of the ports serves as inlet and which as outlet depends on the direction of flow.

Opening through which the flow can enter or exit the flow resistance. Which of the ports serves as inlet and which as outlet depends on the direction of flow.

Parameters

expand all

Choice of flow coefficient to specify. Cv and Kv differ in the physical conditions of their measurement and in the physical units of their expression. Generally at least one of these is reported in product data sheets provided by the manufacturer. Select the option for which data is available.

Flow coefficient expressed in imperial units for a valve opened to full capacity. This is the value reported in the valve data sheets when the Cv coefficient is provided by the manufacturer.

Flow coefficient expressed in SI units for a valve opened to full capacity. This is the value reported in the valve data sheets when the Kv coefficient is provided by the manufacturer.

Flow coefficient expressed in imperial units for a valve that is closed tight and devoid of all flow except for that due to internal leakage between port A and port B. The primary purpose of this parameter is to ensure the numerical robustness of the model during simulation. Its exact value is less important than its being a very small number greater than zero.

Flow coefficient expressed in SI units for a valve that is closed tight and devoid of all flow except for that due to internal leakage between port A and port B. The primary purpose of this parameter is to ensure the numerical robustness of the model during simulation. Its exact value is less important than it being a very small number greater than zero.

Choice of valve opening profile to use during simulation. The selection made here determines how the control signal specified at port L is converted into a valve opening fraction (and opening area). See the block description for detail on the opening parameterizations.

Number by which to divide the exponent in the governing equation of the quick-opening parameterization. Use a value greater than 1 for a true quick-opening profile, one corresponding to a valve that opens quickly from a maximally closed position but progressively more slowly as it approaches the maximally opened position.

Number to which the exponent is applied in the governing equation of the equal-percentages parameterization. This number is the ratio between the maximum and minimum flow rates through the valve (the first corresponding obtained when the valve is maximally opened and the second when the valve is maximally closed). Typical values range from 20 to 50.

Area normal to the flow path at each port. The ports are assumed to be equal in size. The flow area specified here should match those of the inlets of those components to which the valve connects.

Reynolds number at which the fluid in the valve is expected to switch between its laminar and turbulent flow regimes. The switch is assumed to occur at once: the transition region that normally exists between the two flow regimes is ignored.

References

[1] Control Valve Handbook. 4th ed. Marshalltown, IA: Fisher Controls International. 2005.

[2] Flow of Fluids through Valves, Fittings and Pipe. Stamford, CT: Crane, 2010.