Inverting a model for feedforward control
20 次查看(过去 30 天)
显示 更早的评论
I have a process model (first order) for a physical process in the form:
Where are process gain and time constant respectively. = 2.60 and τ = 0.0963
I have already implemented a feedback control using PID control and now want to implement a feedback + feedforward control strategy such that any changes in the (set-point) input are taken care by feedforward controller so feedback sees minimal error. The feedforward controller in this case is inverse of plant dynamics i.e.
How to check if plant model is invertible and compute ?
0 个评论
回答(2 个)
Mathieu NOE
2022-3-2
移动:Joel Van Sickel
2023-4-27
hello
your "feedforward" approach is basically a prefilter in series with your plant. Eeven though the plant may not be strictly invertible , you can do some pole - zero compensation between your filter and the plant. Add some aditionnal high frequency poles , as many as needed to make the filter realisable and stable : the nb of poles of the filter must be equal or greater than its number of zeroes (that are the poles of the plant);
Sam Chak
2022-3-3
移动:Joel Van Sickel
2023-4-27
Since your intention is to have as the final outcome, why not consider the Proportional–Integral (PI) controller?
If the process plant is given by , then designing the PI controller as , where
, and ,
yields the closed-loop transfer function, .
0 个评论