How to get unity power factor in three phase rectifier by hysteresis current controller
显示 更早的评论
attain unity power factor in input side by hysteresis current controller
回答(5 个)
Purushottama Rao
2015-6-20
0 个投票
Steps: 1) Sample the input line voltage signal. Use a PLL for syncronization, the output of which is a unit mag sinusoidal signal inphase with the line voltage. 2) Prepare the ref current. This can be obtained by multiplying the required curret rms value with the PLL output. 3) Measure the input current 4) Calculate the error between the above two currents 5) Define a hystresis controller with the defined hystersis level. Relay block in simulink does this for you. Hystersis limits defines the switching frequency and THD. 6) Pass the output from hystersis to the switches directly.
It should give you the required output. ALL THE VERY BEST
4 个评论
Anees Ansari
2015-6-20
Purushottama Rao
2015-6-22
I propose to have your model or a print screen of it to fix it.
Anees Ansari
2015-6-24
Anees Ansari
2015-6-24
Anees Ansari
2015-6-24
0 个投票
3 个评论
Purushottama Rao
2015-6-25
编辑:Purushottama Rao
2015-6-25
Dear Anees, Thanks for the info. Picture was not clear especially the lower power part Below the diode bridge.I would like to see what is there inside it?
I could not find any return path other than the diode bridge for the phase current. Gv more details. Share your model for better help
Anees Ansari
2015-7-14
Anees Ansari
2015-7-14