Optimal PMU placement with conventional measurements.

Objective function is to optimally place PMU strategically at buses for power system to become completely observable.
265.0 次下载
更新时间 2022/2/14
The monitoring of power grids is an important diagnostic task. This is effectively achieved by the deployment of Phasor Measurement Units (PMUs). PMUs have gained more popularity because of their ability to accurately measure bus voltage and branch current phasors with respect to a Global Positioning System (GPS) clock every few microseconds. Placing PMUs at all locations in a power system network is not economically feasible due to their cost. Therefore, it is necessary to properly distribute PMUs in order to obtain a good estimation of power system states. This problem is known as an optimal PMU placement (OPP) problem. The preliminary objective of an OPP problem is to find strategic locations for PMU placement such that:
• The system is completely observable and
• The solution is economically viable.
When considering the conventional measurements, the optimal placement of PMUs can be formulated as a problem of integer linear programming.
minimize Σ Xk
subject to : 𝑻𝒄𝒐𝒏*𝑷* 𝑻pmu*𝑿 ≥ 𝒃𝒄𝒐𝒏
X= [𝑥1 𝑥2 …𝑥𝑁]𝑇
Xk ∈ {0,1} : PMU placement variable

引用格式

Mohammad Tayyeb Sheikh (2024). Optimal PMU placement with conventional measurements. (https://github.com/sheikhtayyeb/Optimal-PMU-placement-with-conventional-measurements./releases/tag/v1.0.4), GitHub. 检索来源 .

MATLAB 版本兼容性
创建方式 R2021b
兼容任何版本
平台兼容性
Windows macOS Linux
标签 添加标签

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!
版本 已发布 发行说明
1.0.4

See release notes for this release on GitHub: https://github.com/sheikhtayyeb/Optimal-PMU-placement-with-conventional-measurements./releases/tag/v1.0.4

1.0.1

.

1.0.0

要查看或报告此来自 GitHub 的附加功能中的问题,请访问其 GitHub 仓库
要查看或报告此来自 GitHub 的附加功能中的问题,请访问其 GitHub 仓库