For more insight about the per-unit parameterization in transformers please check the documentation of the The Per Unit Conversion.
Three-Phase Transformer (Two Windings)
3 次查看(过去 30 天)
显示 更早的评论
There is an error in the winding's per unit parameter for Leakage Reactance. The mask documentation calls for Leakage Inductance in SI or per unit values. If the Leakage Reactance is expressed as Leakage Impedance per unit the results will be off by 2*pi*f, meaning that SimPowerSystems treats the per unit value input as Reactance (X) not Impedance (L). If the parameters are input in SI units the results are correct. Can TMW please clarify the differences and address the documentation of the parameters. In the documentation discussion of per unit values TMW presents a definition of per unit Inductance. Can TMW provide a reference for this definition and explain where it might be used?