3-phase programmable voltage source output

6 次查看(过去 30 天)
Hello,
I am using a 3 phase programmable voltage source with Amplitude(Vrm Ph-Ph) set to 600 V Phase set to 0 and Freq(Hz) set to 60. I am using a 3ph V-I mesaurement to read the voltages(phase-to-ground). The peak voltage reading from V-I measurement block is coming something around 489.9V. Can someone please explain why is it showing 489V?

采纳的回答

Amish
Amish 2024-4-30
Hi Abhibrata,
When you set a 3-phase voltage source to 600V Phase-to-Phase (Vrm Ph-Ph) and measure the Phase-to-Ground voltage, the expected peak value that you observe is due to the relationship between 'phase-to-phase' and 'phase-to-ground' voltages, as well as between RMS and peak values in AC systems.
The Phase-to-Phase to Phase-to-Ground Relationship is defined as :
This 346.4V is the RMS value of the phase-to-ground voltage.
The RMS to Peak Value Relationship is defined as:
, or,
Therefore, the peak voltage reading of approximately 489.9V for the phase-to-ground voltage is accurate and expected, based on your 600V phase-to-phase setting.
Hope this helps!

更多回答(0 个)

标签

产品


版本

R2017b

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!

Translated by