Controlled Voltage Source (Three-Phase)

31 次查看(过去 30 天)
Yunzhong
Yunzhong 2024-7-23,21:50
评论: Umar 2024-7-25,12:19
After the three-phase voltage signal passes through the Controlled Voltage Source (Three-Phase), the amplitude becomes root three times the original value, and the phase also changes. But according to the module description:
  • Instantaneous — The output voltages, [va vb vc], are equal to the values of the input port S.
The signal input and output should be same..
Could anyone help me this question? Many thanks.
  3 个评论
Yunzhong
Yunzhong 2024-7-24,7:48
Actually I ready set the InputType as ‘Instantaneous‘ but it cause the difference. Its strange.
Umar
Umar 2024-7-24,8:55
Hi Yunzhong,
I concur with your statement.

请先登录,再进行评论。

采纳的回答

Neelanshu
Neelanshu 2024-7-25,11:24
编辑:Neelanshu 2024-7-25,11:24
Hi Yunzhong,
I understand that you are facing an issue with the difference in the value measured by the sensor and the original value. The reason of the discrepancy is that 'Current and Voltage Sensor" block measures phase to phase voltage by default. The phase to phase voltage is square root 3 times the phase to ground voltage.
You can change the 'Voltage measurement type' from phase-to-phase to phase-to-ground voltage. You may refer the following documentation to learn more about the "Current and Voltage Sensor" block:
Hope this helps.
  2 个评论
Yunzhong
Yunzhong 2024-7-25,11:32
Understand. Thank you so much!
Umar
Umar 2024-7-25,12:19
So, it was the setting issue with Current and Voltage Sensor block which makes sense now because that will cause the amplitude to become root three times the original value, and the phase change when using controlled voltage source but glad to know that this issue is resolved.

请先登录,再进行评论。

更多回答(0 个)

类别

Help CenterFile Exchange 中查找有关 Get Started with Specialized Power Systems 的更多信息