Shift Angle of Three-Phase Transformer (Two Windings)
8 次查看(过去 30 天)
显示 更早的评论
The Three-Phase Transformer (Two Windings) has a problem with shift angles. When you use D1 (primary or secondary) there's no shift angle, input and output stay together, but the shift angle should be + or - 30 degrees (images D1_Yg and Y_D1). When you use D11 (primary or secondary) there's a shift angle about + or - 60 degrees, but the shift angle should be + or - 30 degrees (images D11_Yg and Y_D11). I'm not sure if shift angle of harmonic sines or currents fundamental and harmonics is working correctly. Can anyone answer to me if I done something wrong?
Shift angle D1_Yg and Y_D1 (input and output together)


Shift angle D11_Yg and Y_D11 (shift phase of 60 degrees by fourier)


0 个评论
采纳的回答
Sebastian Castro
2016-5-11
I think this is because you're measuring phase-to-phase voltage on the Delta side and phase-to-ground on the Wye side.
If you measure both voltages between phases A and B or both voltages between phase A to ground, you will get the expected phase shifts.
- Sebastian
更多回答(0 个)
另请参阅
类别
在 Help Center 和 File Exchange 中查找有关 Transformers 的更多信息