Voltage measurement problem with isolated system ?

211 次查看(过去 30 天)
Hi everyone.
I have some problems with this simulation. I try to explain: my load is an electric arc furnace and each "controlled voltage source" is the arc voltage. There is a non-grounded star point.
Externally, I have to measure the three phase-to-ground voltages of each arc for control system. (those three voltage measurement blocks) referred to ground.
When I start the simulation I have this problem:
"The Voltage Measurement block 'Voltage Measurement2' is connected between two isolated networks. For a valid measurement, the positive and negative terminals of the block must be connected to electrical nodes that are part of the same electrical circuit. Also check if the ground reference node is defined for that circuit."
I could solve the problem putting a grounded star point load, but it's not the reality. Furthermore, I can't change the secondary winding of MT/BT transformer to Yg because it is delta in reality.
Some ideas? What can I do ?
Thanks.

回答(2 个)

Saad Ullah Khan
Saad Ullah Khan 2021-2-16
Add a large resistance in parallel for each phase.

Joel Van Sickel
Joel Van Sickel 2024-6-10
You would never measure the voltage from a floating source to ground, so there is something wrong in your approach. You can either measure the line to line voltage, and convert it to phase voltage, or ground the system.

类别

Help CenterFile Exchange 中查找有关 Switches and Breakers 的更多信息

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!

Translated by