Phase to phase voltage in Three-Phase Source

24 次查看(过去 30 天)
I'm using Simscape features in Simulink. In the "Three-Phase Source" block the setting of the "Phase to phase voltage" parameter is defined as RMS. But I can not get the nominal values. I can only apply a division by root of 2. Is it right or am I making a mistake?

回答(1 个)

Joel Van Sickel
Joel Van Sickel 2020-9-2
Hello Ademir,
the RMS voltage is Vpeak/sqrt(2). Vline to line = Vphase*sqrt(3). It sounds like you are doing it correctly.
Regards,
Joel
  2 个评论
Maya
Maya 2023-10-5
I am using the Simscape 3 pahse source ( specialized Power systems) to power a 3 phase induction motor. However, I observe that the phase to phase voltages between the three phases are showing slightly different values. None of the values match the setting of the model namely 400V rms. The .slx file is attached.
Joel Van Sickel
Joel Van Sickel 2023-10-9
Hello Maya,
you have your source set to 50 hz but the RMS blocks set to 60 hz. They need to the be same for the calculation to work.
Regards,
Joel

请先登录,再进行评论。

类别

Help CenterFile Exchange 中查找有关 Electrical Sensors 的更多信息

产品


版本

R2016b

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!

Translated by