- You can use regular sample times in your Simulink model to achieve 3 tasks of 100Hz, 1kHz and 10kHz, just mention the different sample times in the blocks that you are using. We create a multitasking scheduler baser on CPU Timer 0 that can schedule the 3 tasks. The fastest task has the highest priority and can preempt the slowest. you can also run in single tasking mode which disables the preemption. I would suggest that you exhaust this somution prior to using other CPU Timers. Enable sample time colors in your model to quickly watch which portion is executing at which rate. Use the rate transition block to send data from one rate to the other.
- Simulink Coder custom code blocks can be used to configure CPU timers (https://www.mathworks.com/help/rtw/ref/systemoutputs.html). You can also use the Memory Copy block to access these timers (https://www.mathworks.com/help/ecoder/ref/memorycopy.html). Keep in mind that CPU Timer 1 is used by our profiler when enabled.
- You don't have to use ePWM interrupts if you don't need them.
F28335 Timer1 & Timer2 Construction - Using via Simulink
9 次查看(过去 30 天)
显示 更早的评论
Hello everyone;
Before the question let me introduce my tools;
C2000 board: F28335
Matlab Model : R2017b
Code Composer: CCS7.4
My question is about using CPU Timer1 and CPU Timer 2 options of this dsp via simulink. As you already now, there are 3 cpu timer in F28335(You can see the
the following figure).
But when I build a Simulink model that containes ADC, ePWM, SCI blocks, model creates(configures) only CPU Timer 0. When I examine the examples of matlab I found "Asynchronous Scheduling" model but in that model 2 different ePwm modules are used as timers because they can trigger subsystems via interrupts. However At the end still timer 0 is used for all timing operations. For example the generated code is seen like this:
My question is how can I implement Cpu Timer1 and Cpu Timer 2 in model so that I can get a code output like following code segment: ? I want to config CPU Timer 1 and CPU Timer 2. and also I don't want ePWM blocks as timers or interrupt sources.
Thanks in advance.
Best regards;
Ömer
0 个评论
采纳的回答
Antonin
2019-4-23
To add to Venkatesh's response:
I hope it helps,
Antonin.
3 个评论
Antonin
2019-4-28
Hi Ömer,
The fastest rate will execute first and then the slower rate executes. If the solwer rate is not completed before the next instance of the fast rate, it will be preempted. Timer 0 will be set to the fastest sample time in the model (base rate), in the example where you have 2 rates of 10kHz and 1kHz, it will be set to 10kHz. Every 10 instances, it will launch the 1kHz task, at that time it allows itself to be preempted (by itself), to allow new fast rates to preempt the slow rate. The result is that your 10kHz task will be running exactly at 10kHz, if the excution time of the 10kHz task is consistent, then the 1 kHz task will also be running exactly at 1kHz. The 1 kHz task may be affected by variation of the excution time of the 10kHz time, that's all, otherwise it's pretty accurate. The 1 kHz task can be preempted by multiple new instances of the 10 kHz task. The same principle applies to all subrates.
In the generated code, ert_main.c is the file where this logic is deployed, while MW_c28xx_csl.c is used to configure interrupts.
You can visualize the scheduling using our profiling example:
https://www.mathworks.com/help/releases/R2019a/supportpkg/texasinstrumentsc2000/ug/real-time-code-execution-profiling.html
This has been heavily used for more than a decade by many people ;-)
Also worth noting, it's important to keep all subrates in the model as an exact multiple of the base rate, to avoid having Simulink create a hidden subrate as a common denominator. For instance, if you have a model with 2 rates of 2 kHz and 3 kHz, Simulink will create a hidden base rate of 1kHz to schedule the 2 tasks. In this case it's not that bad but imagine how fast the hidden base rate would have to be if the 2 tasks are 2.333kHz and 1.334 kHz, in that case the base rate would have to be of 1MHz and kill your performance. I strongly encourage all users to enable sample time colors in their models and be in control of their sample time. The red color is used for the base rate, if you don't see it in your model, it probably means that you have a hidden base rate which may hurt performance. Ctrl+J brings the sample time legend for a mdoel.
I hope it helps,
Thanks,
Antonin.
更多回答(1 个)
Venkatesh Chilapur
2019-4-22
Hi,
Use of Timer1 and Timer2 may not be possible directly from simulink using modelling approach.
Instead a custom code approach using custom code blocks can be used to configure the timer, setup the ISR routine and write the ISR logic. We have custom code blocks under simulink coder that can help.
Could you please share details on why ePWM module are not used for generating interrupts but CPU timers?
Regards,
Venkatesh C
2 个评论
Burak Caykenari
2020-10-23
编辑:Burak Caykenari
2020-10-23
Ömer Bey Merhaba ,
Bu konuda sormak istediğim sorular var size. Mümkünse yardımcı olup dönüş sağlar mısınız ?
caykenarib@hotmail.com
Çok teşekkürler.
另请参阅
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!