Orientation of “Three-Phase V-I Measurement” block and direction of power flow

12 次查看(过去 30 天)
I use “Three-Phase V-I Measurement” block to measure Vabc and Iabc, and then use “Power (3ph, Phasor)” block to calculate P and Q. Could someone please confirm that positive P or Q means that power flows from capital A B C letters on “Three-Phase V-I Measurement” block towards small a b c on the same block. Or is there a completely different logic?
There is a figure on “Power (3ph, Phasor)” block’s help page, but its meaning is not clear to me.

采纳的回答

Rhea Chandy
Rhea Chandy 2020-10-1
Hi!
I understand that you want to know whether positive P and Q implies that power flows from the capital notation ABC letters on the block through the letters abc notation.
Indeed, yes, that is the case regarding the Three-Phase V-I Measurement block. An example,
power_PhasorPowerMeasurements
shows the use of both the Power (3ph, Phasor) block and the three-Phase V-I Measurement block in simscape. This may help you gain an understand of the direction of power flow. The example is listed in the documentation for Power (3ph, Phasor) block.
  1 个评论
Miroslav Blagojevic
Hi Rhea,
Thank you for your answer. I thought that should be the case, and indeed, in some places in my Simulink model that is how the block works. But with one particular subsystem, the block showed opposite of what I expected, and I was pretty sure the subsystem was fine. Thanks to your answer, I found an error in the subsystem, so all is good now. Thank you again. Still think the figure on the help page could be clearer.

请先登录,再进行评论。

更多回答(0 个)

类别

Help CenterFile Exchange 中查找有关 Event Functions 的更多信息

产品


版本

R2017b

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!

Translated by