I want to model 100KVA load operating at 0.9 power factor lagging. What should i set Active Power, QL and QC in load parameters?
3 次查看(过去 30 天)
显示 更早的评论
Hi,
Please help me find the answer to this question:
I want to model 100KVA load operating at 0.9 power factor lagging. What should i set Active Power, QL and QC in load parameters?
0 个评论
采纳的回答
Pemendra Kumar Pardhi
2020-9-29
as per your requirement
Apparent power S= √(P^2+Q^2 ).....................................(1)
And power factor Cosφ= 0.9 lagging, i.e. only inductive load(QL=.. and Qc=0);
Where ϕ= tan^-1(Q/P),.....................................................(2)
from Eq. 1 and 2 you can obtained value of P and QL
更多回答(0 个)