Estimation of Transfer Function of a Setup

1 次查看(过去 30 天)
Dear Experts,
I have an setup with 2416 eurotherm pid controller with thermocouple in feedback, attached to a system. After putting the pid to auto tune mode, am getting the closed loop output graph.
How can i estimate the transfer function of the system.
The Setpoint of PID is known, PID parameters are known, Output response is known. How can i determine the transfer function of the system.
Thanks Nitish

回答(1 个)

Arkadiy Turevskiy
Arkadiy Turevskiy 2013-9-26
You can use System Identification Toolbox to estimate closed-loop transfer function T from setpoint to output. That transfer function is T=GC/(1+GC), where G is plant transfer function and C is controller transfer function.
So if you know T (estimated with System Identification Toolbox) and C (your PID controller), you can calculate G as G=T/(C-TC).
For estimating T, you can use a new algorithm ssarx that we added in R2013b which works well for estimation from closed-loop data. Details are in the release notes.
HTH.
Arkadiy

类别

Help CenterFile Exchange 中查找有关 Linear Model Identification 的更多信息

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!